4. Programming
496791 79
Option 0: (Default) The control unit sends all SIA messages as specified in
Command 131.
Option 1: For full alarm response the control unit sends tampers as burglary
(BA) and sends Contact ID 130 in place of Contact ID 137. In
addition the control unit does not send: FR (fire restoral), PR
(panic restoral), UR (technical restoral), BR (burglary restoral) or
TR (tamper restoral).
Contact ID Options (Command 143)
If you selected Contact ID in Command 103 then use Command 143 to
select the types of contact ID messages that will be sent.
Option 0 Mode Basic, comprises all the messages with numbers in the
“CID Code” column of Fig 23, with the exception of those marked
with an “‡”.
Option 1 Mode Basic + Restore. With this option the system sends all the
messages with numbers in the “CID Code” column of Fig 22.
If the keypad display shows “Custom” when you enter Command 143 then
<Downloader> has been used to program this Command.
Plug by Communicator Outputs (Commands 151 to 158)
The main circuit board of the control unit provides eight programmable
outputs that can be used to control a plug-by communicator. The outputs can
be connected to the communicator by an twelve-way wiring harness provided
with the control unit. See “3. Installation - Fitting a Plug-by Communicator” for
details of the wiring harness.
Commands 151 to 158 allow you to assign one of several channels to each
output. Command 151 controls output 1, 152 output 2, and so on up to
Command 158 which controls output 8. Each Command has the same
options, as follows:
00 Not used 13 Open
01 Fire 14 Close
02 PA 15 Zone Omitted
03 Burglar 16 Medical Assistance
04 Open/Close 17 Key Box
05 Alarm Abort 18 Anti Mask
06 Technical Alarm 19 Smoke Detector
07 Alarm Confirmation 20 Comms Acknowledge (see Note)
08 RF Low Battery 21 Battery Fault
09 Supervision Loss 22 Alarm Partition 1
10 RF Jamming 23 Alarm Partition 2
11 AC Fail 24 Alarm Partition 3
12 Tamper Alarm (Day tamper) 25 Alarm Partition 4
Vedere la pagina 84