4. Programming
32 496791
To change: Key-in: Notes Default
Country PTT Defaults 0 n
n = country, one of:
0 = UK (Y) 5 = France 1 = Ireland 6 = Denmark
1 = Italy 6 = Belgium 2 = OEM 1 7 = Sweden
2 = Spain 7 = Germany 3 = OEM 2
3 = Portugal 8 = Switzerland 4 = OEM 3
4 = Netherlands 9 = Austria 5 = Norway
Note: If you carry out this Command then the system will load all defaults for the
selected country.
Zone nn nn ab nn = zone number 01 to 40 (see Note)
a = Zone type, one of: (default full/part set) (default partitioned)
00 = NU (not used) Z01=FEbcd Z01=FEa
01 = PA (panic alarm) Z02=ERbcd Z02=ERa
02 = FR (fire zone) Z03-Z07=NAbcd Z03=NAa
03 = NA (normal alarm) Z04=NAa
04 = 24 (24 hour zone) Z05=NAa
05 = FE (final exit) Z06=NAa
06 = ER (entry route) Z07=NAa
07 = SA (Shock Analyser) Z08=PA Z08=PAa
08 = TC (Technical) Z09-Z40=NU
09 = KB (Keybox)
10 = SD (Smoke detector) Note: For zones 1 to 9 key in “01” to “09”.
11 = KM (Key switch momentary) For zones 17 to 40 key in “ 17” to “ 40”.
12 = KF (Key switch latched)
13 = AM (Anti mask)
14 = FB (forbikobler zone)
b = Zone attributes, any of:
1 = C (chime)
2 = S (soak test)
3 = D (double knock)
4 = O(Omit allowed)
5 = b (armed in Level B)
6 = c (armed in Level C)
7 = Shock Analyser sensitivity (enter a
number in the range 1 (lowest) to 6
(maximum)
8 = d (armed in Level D)
Example: Zone 17 is a Normal Alarm, active in part set B, that is Omit Allowed.
Type in: 17 Zone Number
03 Normal Alarm
5 Active in Part Set B
4 Omit Allow
to store the value of the Command.
Engineer Code 20 nnnn nnnn = New engineer code 7890