4. Programming
496791 33
To change: Key-in: Notes Default
Zone Configuration 21 0 Close Circuit 4 wire Y
1 End Of Line resistor
2 Fully Supervised Loop
3 8 FSL plus 4 expanders
LS Chime Output 22 n Loudspeaker chime volume
(Single system only.) 0 = Off ( Keypad only)
1=low, 9=max 5
RedCare Reset 23 0 Off Y
1On
Show Panel Account Name 24 (keypad displays name)
Return to programming mode
Internal Sounder 25 0 LS Timed (Follows external bell) Y
1 Continuous
Sounder Delay on Entry 26 0 Bell Delay off
1 Bell Delay on Y
Exit Fault External Sounder 27 0 Internal Y
1 Local
Status Display 28 0 Panel status visible all the time Y
1 Panel status hidden 180s after setting
2 Display for 30 s on valid access code entry
Entry Alarm Delay Time 29 0 Delay off Y
1 Delay on
PA Response 30 0 Audible Y
1 Silent
Zone Tamper Reset 31 0 Engineer reset off
1 Engineer reset on
Keypads and Partitions 32 (See “Keypads and Partitions (Command 32)”)
System Reset 33 0 Eng reset off Y
1 Eng reset on
PA Reset 34 0 PA cust reset Y
1 PA eng reset
First Circuit Lockout 35 0 Lock out on Y
1 Re-arm
Alarm Abort 36 0 Abort off Y
1 Abort on
Day Tamper Comms 37 0 Day Tamper off Y
1 Day Tamper on
System Tamper Reset 38 0 Customer Reset
1 Engineer Reset Y