4. Programming
36 496791
To change: Key-in: Notes Default
Level B Alarm response 63 n
For a single system n is one of the following:
0 Keypad sounder Only
1 Internal sounder and keypad sounders Y
2 Local (all sounders, no comms)
3 Full alarm (all sounders and comms)
For a partitioned system n is one of:
0 Keypad sounder Only
1 Local alarm
2 Full alarm Y
Level B Entry Time 64 1 10 seconds
2 20 seconds Y
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
Level B Exit Time 65 1 10 Seconds
2 20 seconds Y
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
Level C Final Exit Operation70 0 C=FE = FE (Final exit) Y
(Single system only.) 1 C=FE = NA (Normal alarm)
Level C Entry Route 71 0 C=ER = ER (Entry route) Y
(Single system only.) 1 C=ER = FE (Start entry timer)
Level C Exit Mode 72 n
For a single system n is one of the following:
0 Timed plus low tone (default)
1 Instant set
2 Silent set (kpd beeps at end of setting period)
3 Exit mode same as Level A
For a partitioned system n is one of:
0 Timed full tone Set (default) 3 Instant set
1 Terminated 4 Silent (kpd beeps at end of setting period)
2 Final door 5 Lock Set