4. Programming
496478 49
then close down and dial the second telephone number and
attempt to connect to the remote receiver. If received and
acknowledged on this attempt, the system will close down
and the alarm transmission will be complete. If the system
fails to connect to the second telephone number, it will close
down again and re-attempt to connect to the first telephone
number. The system will continue to shuttle between the
two numbers up to 15 times.
Dual (3) Reports to two different receiver numbers (see Com-
mands 115 and 116).
Operation: The communicator dials the first telephone
number and attempts to connect to the first central
station. If received and acknowledged, the communicator
dials the second number and attempts to transmit to the
second central station. If received and acknowledged by
the second number, the communicator will close down
and the alarm transmission will be complete. If calls to the
first number fail, then the communicator attempts to call
the second number. If the communicator fails to connect
to the second telephone number, it will close down again
and re-attempt to connect to the first telephone number.
The communicator will continue to shuttle between the
two numbers, calling each number up to 15 times, until it
has successfully called both numbers.
Note: Dual reporting does not work with SIA or CID reporting formats.
Reporting Type (Command 103)
The system offers four message formats:
Option 0 Scancom Fast
Option 1 Contact ID
Option 2 Scancom SIA Level I
Option 3 Scancom SIA Level II (does not send time and date).
Line Fail Response (Command 106)
This command lets you program the system to respond with either audible or
silent alarms when the system detects a fault on an attached telephone line.
The exact response depends on whether the system is set or unset, as
follows:
Disabled (0) The control unit does not monitor the telephone line.
Audible (1) If the system is unset then the system logs the event. The
keypad produces a short audible tone every minute.