3. Installation
Detector Circuit Connections
The left hand edge of the main PCB provides 14 connectors that can be used
for up to 8 zones.
Four Wire CC Connections
Figure 12 shows how to connect four wire CC zones. Note that pairs of alarm
contacts share contacts. You should wire the tamper contacts of all detectors
in series and then connect them to the contacts marked "A/T".The control
panel provides enough connectors for eight four wire circuits. If you wish to
connect 16 four wire circuits you must fit a 9755 hardwired expander card
(see "Connecting a 9755 Expander").
Alarm contacts
Tamper Contacts (in series)
Alarm contacts
CCT1
CCT2
CCT3
CCT4
CCT5
CCT6
CCT7
CCT8
A/T
Alarm contacts
Alarm contacts
Zone 09
Tamper contacts for zones 09 to 16.
CCT9
CCT11
CCT10
CCT12
A/T
Zone 10
Zone 11
Zone 12
9750 9755
Figure 12. Four Wire Closed Circuit Connections
Connecting a 9755 Expander
Figure 13. shows how to wire a 9755 Expander to the control unit.
0V 12V CLK DATA
To other keypads
12V
0V
DATA
CLK
9750HWX
Control Unit
Figure 13. Connecting a 9755 Expander
Once you have connected an expander refer to the instruction supplied in
order to connect detectors.