Installer Mode Programming i-on40
Page 76
program Line Fail Response select Communications – Line
Fail Response.
The exact response depends on whether the system is set
or unset, as follows:
Disabled.
The control unit does not monitor the telephone line.
Audible.
If the system is unset then the system logs the
event. The keypads produce a short audible tone
every minute. Entering a valid access code silences
the sounders and the display indicates a telephone
line fault. The system can be set again with the line
fault present.
If the system is set then the control unit logs the
event but does not give any tone or display. The
control unit cancels any programmed siren delay if
the line is out of order when an alarm occurs.
Note: Cooper Security recommend audible response for
line fault.
Silent.
If the system is unset then the display indicates a
telephone line fault and the control unit logs the
event. The system may be set again with the line
fault present.
If the system is set then the control unit does not
give any indication or tone but does log the event.
The control unit cancels any programmed siren delay
if the line is out of order when an alarm occurs.
Line Fail Delay
This menu controls the length of time that the control
unit waits until starting an alert if the communications
line fails. The values available are 0 to 60 seconds.
IP Network (Own)
This menu allows you to:
a) Give the control unit its own IP (Internet Protocol)
address, used for the built in Web Server
Vedere la pagina 79